Sycon 2702

Print

The SYCON 2702 is a titration device ideal for use in a water softening system or for the protection of a reverse osmosis. The limit value to be monitored and the measuring interval can be freely programmed. In addition, relay contacts and a 4 ... 20 mA interface enable connection to a large number of controls. The measured values are stored on an internal SD card. The device has an optional cloud connectivity.

 

 

The special features of the Sycon 2702 analyzer include:

  • easy commissioning
  • intuitive operation
  • low maintenance
  • self-calibrating
  • diagnostic program
  • documentation of measurement results on an SD card
  • 4...20 mA interface
  • optional cloud connectivity
  • maintenance-free full-colour sensor
  • tool-free maintenance of the measuring chamber


The following functions are reliably displayed by the Sycon 2702 analyzer:

  • individually selectable limit value in the measuring range of the reagent used
  • alarm in case of lack of reagent
  • graphic display (illuminated)
  • various languages
  • analysis startup options:
    • automatically by time interval
    • suppression of the analysis via current switch
    • analysis via external control


 The limit value is set individually.

Article number 30-010162
Parameter Value / Range
Supply voltage 85 ... 264 VAC at 47 ... 440 Hz
Power consumption 25 VA (operating)
Protection class IP 43 - with housing IP 54
Ambient temperature 10 ... 45 °C
Temperature of measuring water 5 ... 40 °C
Humidity 20 ... 90 % RF not condensing

 

Parameter Value / Range
Installation wall mounting in closed rooms
Dimensions on wall holder:
274 x 275 x 130 mm
with housing (has to be ordered separately):
330 x 300 x 185 mm
Weight on wall holder: 1,9 kg
with housing: 3,7 kg
Relais outputs 2 relays
250 VAC / VDC 4 A
potential free outputs NC/NO
  • alarm "limit value"
  • dysfunction of analyzer
Signal input potential free input contact
Supply intake/outlet

tubes with 6 mm outer diameter

 

 

 

Parameter Value / Range
Measuring principle colorimetrical method
Measuring range
Total hardness Carbonate hardness unit
0,012 ... 30 0,3 ... 22,5 °dH
0,015 ... 37,6 0,4 ... 28,2 °e
0,021 ... 53,4 0,5 ... 40 °fH
0,214 ... 534 5,34 ... 400 ppm
Reagent consumption < 0,05 ml / analysis (soft water)
up to 10.000 analyses per 500 ml bottle
Shelf-life of reagent 24 months
Water consumption approx. 1000 ml / analysis
The water consumption varies depending on the inlet pressure and the flushing duration.
Inflow pressure approx. 0,5 ... 5 bar
If the inlet pressure exceeds 2 bar a pressure reducer has to be used.
Water sample clear, colourless, without solids, without gas bubbles
Parameter Value Unit
ph 4 ... 10,5   
iron < 3 ppm
copper < 0,2 ppm
aluminium < 0,1 ppm
manganese < 0,2 ppm
acid capacity KS 4.3 < 5 mmol/l

 

 

Ask about this product