Sycon 2502

Print

The SYCON 2502 is an analyzer for limit value monitoring. It includes a demand-controlled regeneration release and a monitoring of the condensate return for your boiler house. The limit value of the analyzer SYCON 2502 is determined by the reagent used and controlled at fixed time intervals. If the limit value is exceeded, a signal is sent to the controller.

The special features of the Sycon 2502 analyzer include:

  • easy commissioning
  • intuitive operation
  • low maintenance
  • self-calibrating
  • diagnostic program
  • maintenance-free full-colour sensor
  • tool-free maintenance of the measuring chamber


The following functions are reliably displayed by the Sycon 2502 analyzer:

  • monitoring of a limit value determined by the reagent used
  • alarm "lack of reagent"  / BOB functionality
  • detailed LED status display
  • language neutral
  • analysis startup options:
    • fully automatic according to time interval
    • suppression of the analysis by means of control switch
    • analysis via an external control


 The limit value is determined by the reagent used.

Article number 30-010128
Article description Sycon 2502
Scope of delivery Analyzer, manual
Parameter Value / Range
Supply voltage 85 ... 265 VAC at 47 ... 440 Hz
Power consumption 25 VA (operating)
Protection class IP 43 - with housing IP 54
Ambient temperature 5 ... 45 °C
Temperature of measuring water 5 ... 40 °C
Humidity 20 ... 90 % RF not condensing

 

Parameter Value / Range
Installation wall mounting in closed rooms
Dimensions on wall holder:
274 x 275 x 130 mm
with housing (has to be ordered separately):
332 x 345 x 190 mm
Weight on wall holder: 1,9 kg
with housing: 3,8 kg
Relais outputs 3 relays
250 VAC / VDC 4 A
potential output NC/NO
  • alarm "limit value"
  • dysfunction of analyzer
  • analysis active / cooling water
Signal input potential free contact entry
Supply intake/outlet

tubes with 6 mm outer diameter

 

Parameter Value / Range
Measuring principle colorimetric method
The limit value is defined by the reagent used
Total hardness limit value reagents
0,02 °dH 0,05 °dH 0,10°dH  
0,20°dH  0,30°dH 0,50 °dH  
1°dH 2°dH 3°dH 5°dH

 

Carbonat hardness limit value reagents
1 °dH 1,5 °dH 2 °dH 3 °dH 
Reagent consumption < 0,10 ml / analysis
min. 5000 analyses per 500 ml bottle
Shelf-life of reagent 24 months
Water consumption approx. 1000 ml / analysis
The water consumption varies depending on inlet pressure and flushing duration
Pressure of inflow approx. 0,5 ... 5 bar
If the inlet pressure exceeds 2 bar a pressure reducer has to be used
Water sample clear, clourless, free of solids, without gas bubbles
Parameter Value Unit
ph 4 ... 10,5   
iron < 3 ppm
copper < 0,2 ppm
aluminium < 0,1 ppm
manganese < 0,2 ppm
acid capacity KS 4.3 < 5 mmol/l

 

 