The SYCON BoB is an online analysis device for monitoring soft water for operation without constant supervision for safe operation during 72 hours (BOB 72 hours). The additional relay contacts make it possible to control an external cooling water valve for a sample cooler. The device status can be connected to remote maintenance via the existing RS-485 interface with Modbus-RTU protocol.
Specifications
Parameters | value / range |
Power supply | 85 ... 265 VAC at 47 ... 440 Hz |
Power consumption | 25 VA (peak) |
Protection class | I |
degree of protection | IP54 |
Ambient temperature | 10 ... 45 °C |
Measuring water temperature | 5 ... 40 °C |
Sample Port | Hose 6mm |
Dimensions (W x L x D) | 274x275x130mm |
Weight | 3.8kg |
Operating pressure | 0.5 .. 5 bar |
Reagents | H25-0.05 H25-0.1 |
Durability reagent | 24 months |
Approved according to VdTÜV leaflet BP WAUE 0100
Artikelnummer | 30-610164 |
Artikelbezeichnung | Analysis device SYCON BOB in housing, 230V |
We manufacture our reagents ourselves. Only high-quality raw materials are used. Each production batch is checked in our laboratory for the specified limit value.
Reagent | Article number | Threshold | ||||
Single Bottle | Value Pack | °dH | mmol/l | Boiler type | Norm | |
H25-0.05 | 32-084125 | 32-484125 | 0.03 | 0.005 | Circulation boiler | EN12952-12 |
H25-0.1 | 32-084135 | 32-484135 | 0.05 | 0.01 | Large water boiler | EN12953-10 |
We also offer accessories for our devices for easy installation and maintenance
Description | Article number | Description |
SYCON connection set | 33-000701 | For connecting a SYCON analyzer to a sample line with 1/2" or 1/4"
|
Pressure reducer with filter incl. manometer for SYCON |
33-090738 | Recommended for inlet pressures above 2 bar
|
Cleaning set SYCON Clean | 30-010900 | Cleaning set for measuring combs
|
Cleaning liquid FIT3000 | 32-089100 | Cleaner for measuring chambers (1000 ml) |
Maintenance set SYCON 2702- 2802 / FE / BOB |
32-089100 | Spare parts set for SYCON 2702 - 2802 / FE / BOB
|